Status (05h)
Read the OT status register to determine which channel
recorded an overtemperature condition. Bit D7 is high if
the fault reading occurred from channel 1. Bit D6 is
high if the fault reading occurred in channel 2. The OT
status register is cleared only by reading its contents.
After reading the OT status register, a temperature reg-
ister read must be done. Reading the contents of the
register also makes the OT output high impedance. If
the fault is still present on the next temperature mea-
surement cycle, the corresponding bits and the OT out-
put are set again. The POR state of the OT status regis-
ter is 00h.
OOTT
Mask (06h)
Set bit D7 to 1 in the OT mask register to prevent the
OT output from asserting on faults in channel 1. Set bit
D6 to 1 to prevent the OT output from asserting on
faults in channel 2. The POR state of the OT mask reg-
ister is 00h.
2-Channel Temperature Monitor with Dual Automatic
PWM Fan-Speed Controller and Five GPIOs